Place of Origin : 
            Post Date : 22-09-2021
                        Expiry Date : 29-10-2024
         
Breaker Switch Unit With Encapsulated Vacuum Interrupter
Each Vacuum Interrupter Is Embedded In A Solid-insulated Pole Made Of Weather-proof Cyclo Aliphatic Epoxy Resin. This Enables A Small Design As Well As Resistance Against Environmental Effects. The Breaker Switch Unit Is Comprised Of Three Poles, The Operating Mechanism, And The Operating Mechanism Housing.
The Sequence Of The Poles Is A -B €“ C Or 1 €“ 2 - 3 (sequence Left To Right When Viewed From The Lower Terminal Side Of The Recloser Switch Unit.
Breaker Principle And Design Of 36KV Vacuum Circuit Breaker
ZW32 Series Breakers Are Used In Distribution Systems. Circuit Breakers Are Used To Make And Break Normal And Fault Currents. Breakers Are Fully Equipped With Sensors And A Controller To Provide A Means Of Protection And Control. In Case Of A Line Fault, Breakers Can Break And Make Currents Several Times, Thus Avoiding Longer Network Interruptions Due To Temporary Faults. The Manufacture, Design, And Testing Of The Vacuum Recloser Is Based On Current Standards IEC 62271-100.
Technical Parameters Of 33KV Vacuum Circuit Breaker
Table 1-Circuit Breaker Rated Technical Data
No.	Name	Unit	Parameter
1	Rated Voltage	KV	36
2	1 Min Rated Power Frequency Withstand Voltage		70
3	Rated Lightning Impulse Withstand Voltage (peak)		170
4	Rated Current	A	630
5	Rated Frequency	Hz	50/60
6	Rated Short-circuit Breaking Current	KA	12.5
7	Rated Short-circuit Making A Current (peak)		31.5
8	Rated Peak Withstand Current		31.5
9	Rated Short-time Withstand Current (4s)	KA	12.5
10	Rated Operating Sequence		O-0.3s-CO-180s-CO
11	Closing Time	Ms	25-60
12	Opening Time		18-45
13	Breaking Times For Rated Short-circuit Breaking Current	Times	30
14	Mechanical Life		10000
15	Secondary Circuit 1min Power Frequency Withstand Voltage	V	2000
16	Charging Motor Rated Power	W	40
17	Charging Motor Rated Voltage	V	DC24
18	Rated Closing Operation Voltage		DC24
19	Rated Opening Operation Voltage		DC24
20	Motor Charging Time	S	=12
21	Weight	Circuit Breaker	Kg	130
		A Circuit Breaker With Dis-connector		165
Table 2 - Main Mechanical Characteristics Of Circuit Breaker
No.	Name	Unit	Parameter
1	Contact Travel	Mm	12-14
2	Contact Over-travel		2-4
3	Phase Distance (Center To Center)		410±2
4	Contact Closing Bounce Time	Ms	=3
5	Three-phase Open/close Synchronism		=2
6	Average Opening Speed	M/s	1.2-1.6
7	Average Closing Speed		0.6-1.0
8	Resistance Of The Main Circuit	µO	=200
Table 3 €“ Main Technical Data Of Dis-connector
No.	Name	Unit	Parameter
1	Rated Voltage	KV	36
2	Rated Current	A	630
3	Frequency	Hz	50/60
4	Short-time Withstand Current (4s)	KA	12.5
5	Rated Peak Withstand Current		31.5
6	1min Power Frequency Withstand Voltage	Across Open Contacts	KV	
70
7	Circuit Resistance	µO	=120
8	Center Deviation Value Of Three-phase Insulating Closing	Mm	=2
9	Synchronism Deviation Value Of Three-phase Insulator Open/close		=2
10	Insulating Distance Between Conductor To Earth		=300
11	Contact Travel		=260
Table 4 €“ Operating Mechanism Characteristics
No.	Name	Unit	Parameter	No.
1	
Opening Coil
	DC24	7	Reliable Tripping Under 65%-120% Rated Voltage, No Tripping Less Than 30% Rated Voltage
		DC110	5	
		AC220	3.5	
		DC220	1.8	
2	
Closing Coil	DC24	7	Reliable Tripping Under65%-120% Rated Voltage
		AC220	3.5	
		DC220	1.8	
3	Overcurrent Tripping Coil		8	
4	Energy Charging Motor	Rated Voltage: DC/AC220V
Rated Power: 40W	Reliable Tripping Under85%-110% Rated Voltage
5	Closing Spring Charging Time	=10s	
Zhuhai Gopower Smart Grid Co., Ltd. Is One Of The Earliest 33 Kv Vcb Manufacturer. We Provide 33kv Automatic Circuit Recloser, 33kv Pcvcb, 33kv Outdoor Vcb, Vcb 33kv And Etc. Want To Know 33kv Auto Recloser Price Or 33 Kv Vcb Price? Please Contact Us.