three phase energy meter test equipment - Product
Place of Origin : Haiyan,China
Delivery Terms : FOB,CIF,CNF,DDP,DDU
Delivery Time : 35 Days
Product Capacity : 30 Sets Per Month
Payment Terms : T/T Or L/C
Product Description
Three-phase Meter Test Bench is a new generation, high precision, multifunctional energy meter calibration equipment. It uses the international’s most advanced technology and components available in 90 decade .It can be widely used to calibrate single /three phase energy meter or multifunction energy meter accuracy 0.2% or under.
Basic Information
Brand : Shengdi
Model : HS-6303
Material : Aluminium,copper,plastic
Expiry/Validation Period : 30 Days
Physical Specification
Other Specification : TECHINCAL SPECIFICATION
1. Accuracy Class: 0.05/0.1
2. Reference Meter (Standard Meter):
HS-5300 Three-phase Standard Energy Meter
Accuracy Class: 0.05/0.1
Input Range: 3 × (40V~480V),
3 × (0.01A~120A),
3. Output:
Output Voltage: 3 ×0~300V
Output Current: 3 ×0~100A(option 200A)
4. Output Capacity For Each Phase
Voltage: 0~800VA
Current: 0~1500VA
5. Adjustable Range:
Voltage:0-120% Fine Adjustment: 0.01%
Current:0-120% Fine Adjustment: 0.01%
Phase: 0-360.0° Fine Adjustment: 0.1°
Frequency: 45-65Hz, Fine Adjustment: 0.01Hz
6. Output Stability (Power Factor) :< 0.05% / 3min (PF=1.0)
7. Waveform Distortion :< 0.5 %( Voltage / Current)
8. Harmonic Wave Output
2-21 Harmonic Waves,
Contents Of Harmonic Wave (Voltage &Current< 40%)
Harmonic Phase: 0°~359.99°
9. Starting Current Output: 1mA (min.)
10. Meter Type: Various Kinds Of Single Phase/3 Phase Active/reactive Energy Meter (includes Sine Wave, Var 90°, Var 60°), Mechanical Type, Electronic Type, Multifunction And Four Quadrants Energy Meter.
11. Meter Positions: 6-40
12. Control Mode:
A. Keyboard Control: LCD Menu, Fully Automatic, Manual Calibration.
B. Software Control: Under Windows 98/2000/XP System, Fully Automatic, Self-definition Calibration.
13. Functions:
A. Error Test
B. Standard Deviation (S) In Error Test
C. Creep Test (no Load Test)/automatic/manual Operation
D. Initial Test (starting Test)/automatic/manual Operation
E. Phase Rotation Test
14. Database Providing With Static, Information Check, Management, Printing.
15. Power Supply: 3×220/240V±15%(option 120V), 50/60 Hz