Place of Origin : Wuhan,China
Series resonance device is mainly designed and manufactured for communication voltage endurance test of 11kV/30MW hydro-generator. Two separate designs are adopted for reactor.
Series resonance device is mainly composed of frequency conversion control power supply excitation transformer reactor and capacitor voltage divider.
| Rated Output Voltage | 0~50kV(AC RMS) |
| output Frequency | 45~65Hz |
| Resonance Voltage Waveform | Pure Sine Wave Waveform Distortion Rate≤1.0% |
| Work System | Under Full Power Output Normally Continuous Work Time5min |
| quality Factor | 10~40 |
| Frequency Regulation Sensitivity | 0.1Hz,Instability<0.05% |
| Maximum Test Capacity | 5000kVA And Below |
| Working Power Supply | 220V And 380V±10%,Power Frequency 50Hz±5% |