Copper / Aluminium Conductor XLPE Insulated PVC Sheathed Medium Voltage Power Cable - Product
Place of Origin : Beijing,China
Delivery Time : Negotiable
Product Description
Copper / Aluminium Conductor XLPE Insulated PVC Sheathed Medium Voltage Power Cable
1.Product standard
GB12706-91, GB/T18380.3-2001(IEC502 IEC332-3)
2.specifications and names
- - - -
Type | Designation |
Copper conductor | Aluminium conductor |
ZRYJV | ZRYJLV | XLPE insulated and PVC sheathed fire retardant power cable |
ZRYJV22 | ZRYJLV22 | XLPE insulated, steel tape armored and PVC sheathed fire retardant power cable |
ZRYJ
Physical Specification
Other Specification :
Copper / Aluminium Conductor XLPE Insulated PVC Sheathed Medium Voltage Power Cable
1.Product Standard
GB12706-91, GB/T18380.3-2001(IEC502 IEC332-3)
2.specifications And Names
- - - -
Type | Designation |
Copper Conductor | Aluminium Conductor |
ZRYJV | ZRYJLV | XLPE Insulated And PVC Sheathed Fire Retardant Power Cable |
ZRYJV22 | ZRYJLV22 | XLPE Insulated, Steel Tape Armored And PVC Sheathed Fire Retardant Power Cable |
ZRYJV32 | ZRYJLV32 | XLPE Insulated, Steel Wire Armored And PVC Sheathed Fire Retardant Power Cable. |
ZRYJV42 | ZRYJLV42 | XLPE Insulated, Crudewire Armored And PVC Sheathed Fire Retardant Power Cable. |
ZRVV | ZRVLV | PVC Insulated, PVC Sheathed Fire Retardant Power Cable. |
ZRVV22 | ZRVLV22 | PVC Insulated, Steel Wire Armored AndPVC Sheathed Fire Retardant Power Cable. |
ZRVV32 | ZRVLV32 | PVC Insulated, Steel Wire Armored And PVC Sheathed Fire Retardant Power Cable |
ZRVV42 | ZRVLV42 | PVC Insulated, Crudewire Armored And PVC Sheathed Fire Retardant Power Cable. |
- - - -
3.Operating Characteristics
1).(U0/U)0.6/1KV, 3.6/6KV, 6/6KV, 6/10KV, 8.7/10KV, 8.7/15KV, 18/20KV, 21/35 KV, 26/35KV.
The Rated Voltage(U0/U)0.6/1KV, 3.6/6KV, 6/6KV, 6/10KV, 8.7/10KV, 8.7/15KV, 18/20KV, 21/35 KV, 26/35KV.
2). Max. Permissible Continuous Operating Temperatures Of Conductor Not Exceed 90C, Max. Short-circuit Temperature Of Conductor Shall Not Exceed 250C. (5s Max. Duration)
3).The Ambient Temperature Under Installation Shall Not Below 0C, The Min. Bending Radius: Not Less Than 8 Times For The Cable Of External Diameter No More Than 40mm; Not Less Than 16 Times For The Others.
4.Test Voltage Of Cable
- - - -
Rated Voltage KV | 0.6 | 1.8 | 3.6 | 6 | 8.7 | 12 | 18 | 21 | 26 |
Test Voltage KV | 3.5 | 6.5 | 12.5 | 21 | 30.5 | 42 | 63