JB3855 - 1996 VS1 Rated Short - Circuit Duration 4s Indoor 12kV Vacuum Circuit Breaker
Main specifications and technical parameters(Refer to Tab 1)
Tab 1
- - - -
No | Item | Unit | Technical data |
1. | Rated voltage | KV | 12 |
2. | Rated short-time Power frequency withstand voltage (1min) | 42 |
3. | Rated lightning Impulse withstand voltage (peak value) | 75 |
4. | Rated Frequency | Hz | 50 |
5. | Rated current | A | 630 1250 | 630  1250 1600  2000 2500  3150 | 1250 1600 2000  2500 3150  4000* |
6. | Rated short circuit breaking current | KA | 25 | 31.5 | 40 |
7. | Rated short time withstand current | 25 | 31.5 | 40 |
8. | Rated short-circuit duration | S | 4 |
9. | Rated peak value withstand current | KA | 63 | 80 | 100 |
10. | Rated short-circuit closing current (peak value) | 63 | 80 | 100 |
11. | Secondary circuit power frequency Withstand voltage(1 min) | V | 2000 |
12. | Rated single/ back-to-back capacitor bank Breaking current | A | 630/400 (40 kA for 800/400) |
13. | Rated capacitor bank making rush Current | KA | 12.5(frequency No more than 1000Hz) |
14. | Opening time | Ms | 20~50 |
15. | Closing time |  | 35~70 |
16. | Mechanical life | Time | 10000   30000   60000 |
17. | Breaking times at rated short-circuit current | Time | 50 (40 kA for 30) |
18. | Permissible wear accumulated thickness Of moving and fixed contact | Mm | 3 |
19. | Rated operating voltage of closing | V | AC 110/220   DC 110/220 |
20. | Rated operating voltage of opening | AC 110/220   DC 110/220 |
21. | Rated operating voltage of motor | AC 110/220   DC 110/220 |
22. | Rated power of closing | W | 80 |
23. | Stored energy time | S | ≤15 |
24. | Contact clearance | Mm | 11±1 |
25. | Super travel |  | 3.5±1 |
26. | Contact closing bounce time | Ms | ≤2 |
27. | Different duration of three-phase opening And closing |  | ≤2 |
28. | Average opening speed(refers to the average speed For first 6mm after opening of breaker contact) | M/s | 0.9~1.2 |
29. | Average closing speed(refers to the average speed  for last  6mm before closing of breaker contact) |  | 0.5~0.8 |
30. | Contact opening bounce amplitude value | Mm | ≤3 |
31. | Conductance circuit resistance | µΩ | ≤50 (630A) ≤45 (1250A) ≤35(1600 ~ 2000A) ≤25(over  2500A) |
32. | Contact closing contact pressure | N | 2400±200 ( 25 kA ) 3100±200 ( 31.5 kA ) 4250±250 ( 40 kA ) |
33. | Rated operating order     |  | Opening -0.3S- closing/ Opening -180S-v |
- - - -
Outline Dimension Drawing
Dear friends,  pls contact us for the outline dimension drawing, We will give you quick reply.
Summary
VS1(ZN63A) series vacuum breaker is of indoor high voltage switchgear suitable for 12kV .
Three-phase power system with 50Hz frequency in order to protect and control electrical appliances, And especially suitableÂÂ
For frequent operation at rated current or incessant open circuit due to unique advantages of vacuum circuit breaker.
Spring operating mechanism and breaker body parts adopt integration design.Thank for this design,
 breaker not only can be a fixed installation unit , ÂÂ
But also can be a withdraw-able unit with a specially pushing framework.For meet the requirement of XGN2,
GG1A cabinet , The fixed type breaker can be install additionally interlock. ÂÂ
ÂÂ
2Expression mode of product model
                     V S 1 - 12 / □-□
        Rated short circuit breaking current kA
ÂÂ
Rated current A
Rated voltage kV
3Product Reference StandardÂÂ
Shall be in accordance with standards in GB1984-89 Alternating Current High Voltage Breaker, ÂÂ
JB3855-1996 3.6~40.5kV Indoor Alternating Current High Voltage Vacuum Breaker, ÂÂ
And DL403-1999 Specification for Order of 10~35kV Indoor High Voltage Vacuum Breaker, ÂÂ
And subject to relative requirements in IEC56 (87 publication).
ÂÂ
4Operating environment condition
A) Normal operating environment condition
Highest temperature:                     +40ºC
Lowest temperature:                      -15ºC
B) Environment humidity
Daily average relative humidity:       ≤95%
Monthly average relative humidity:       ≤90%
Daily average saturated vapor pressure:  ≤2.2×10-3 MPa
Monthly average saturated vapor pressure:   ≤1.8×10-3 MPa
C) Altitude: below 1000m area;
D) Earthquake intensity: no more than 8 degree;
The product shall be away from weep,  fire and explosion,  chemical corrosion and strenuous vibration place.