GB1984 Conductance Circuit Adopts Front And Rear Layout 12kv VMD2 Vacuum Circuit Breakers
Technical Parameters
- - - -
NO | Item | Unit | Technical Date |
1 | Rated voltage | KV | 12 |
2 | Rated insulating level | Rated short time power  frequency withstand voltage(1min)          | 42 |
Raed lighting inpulse Withstand voltage (peak value)              | 75 |
3 | Rated Frequency | Hz | 50 |
4 | Rated current | A | 630 | 630 | 1250 | 1250 |
1250 | 1250 | 1600 | 1600 |
  |   | 2000 | 2000 |
2500 | 2500 |
3150 | 3150 |
4000 | 4000 |
5 | Rated short circuit breaking current        | KA | 20 | 25 | 31.5 | 40 |
6 | Rated short time withstand current           | 20 | 25 | 31.5 | 40 |
7 | Rated peak withstand current  | 50 | 63 | 80 | 100 |
8 | Rated short-circuit closing current (peak value) | 50 | 63 | 80 | 100 |
9 | 4S rated short-time withstand current  4s | 20 | 25 | 31.5 | 40 |
10 | Rated shock steady current | 50 | 63 | 80 | 100 |
11 | Rated making surge current of capacitor bank | 12.5(The frequency is less than 1000Hz) |
12 | Rated breaking current of single/symmetrical capacitor bank | A | 630/400 (The value shoule be 800/400 While the current is 40kA)                                 |
13 | Duration of rated short-circuit current | S | 4 |
14 | Power frequency withstand voltage of secondary circuit | V | 2000 |
15 | Rated operationl voltage | Making coil | AC110/220   DC110/220 |
Breaking coil | AC110/220   DC110/220 |
Energy-storage motor | AC110/220   DC110/220 |
16 | Making time  (under Rated voltage) | Ms | 35-70 |
17 | Brealing time(under Rated voltage) | 20-45 |
18 | Permitted abrasion thickness of moving and fixed contacts | Mm | 3 |
19 | Energy storage times | S | ≤15 |
20 | Contactor space | Mm | 9± 1 |
21 | Contacting travel | 3---4 |
22 | Bounce time of Contactor during making | Ms | ≤2 |
23 | Different time of breaking / making of 3 phases | ≤2 |
24 | Average breaking speed | 0.9-1.3 |
25 | Average making speed | 0.4-0.8 |
26 | Rebound amplitude of contact breaking | Mm | ≤3 |
27 | Conductance circuit resistance | µΩ | ≤50 (630A) |
≤45(1250A) |
≤35(1600A-2000A) |
≤25(More than 2500A) |
28 | The contacting pressure of of contactor during making | N | 2000±200(20kA) |
2400±200(35kA) |
3100±200(31.5kA) |
4750±250(40kA) |
29 | Rated operating sequence |   | O- θ -CO-180s-CO |
The average breaking speed is that of contactor’s first 6mm . The average making speed refers to the average speed of total Contactor space . When the rated short circuit breaking current is less than 40kA,  θ is equal to 0.3S. When the short circuit breaking current is more than or equal to  40kA,  θ is equal to 180S |
- - - -
Summary
The VMD2 series indoor circuit-breaker is our independent developed new generation 12 kv vacuuum circuit breaker.ÂÂ
Its main characters as follows: the conductance circuit is installed in an three-phase insulating sleeve ,
 its mechanism and conductance circuit adopts front and rear layout.ÂÂ
And the mechanism is our deveoped new design,  with simple construction,
 reliable operation, And rich manufacturing experiences of million sets , ÂÂ
Used  and learned by many high-end vacuum circuit breaker manufacturers.
ÂÂ
Technical standard
All the technical parameters of breaker completely satisfy the Standards Of GB1984 AC Highvoltage Breaker, ÂÂ
GB/T 11022 -1999 Common Specifications For High-Voltage Switchgear And Controlgear Standards, ÂÂ
China Power Sector Standards DL403.
Also meet the requirements of IEC62271-100,  IEC56 and other main industrialized country’s similar standards
ÂÂ
Testing
VMD2 series circuit breaker have passed has passed followingÂÂ
Test ,  to ensure the product’s safe Operation.
ÂÂ
Type tests : power-frequency withstand voltage tests ,  lighting impact withstand voltage tests,  , ÂÂ
Temperature rising tests,  short-time withstand current tests , ÂÂ
Peak withstand current tests , Short circuit breaking ability tests ,  mechanical lift tests, Ect
ÂÂ
Routine test before out of factory: mechanical performance test  ,  power-frequency withstand voltage tests of the main circuit , ÂÂ
Insulating property  tests on control and auxiliary circuits , Measurement of ther resistance of the main circuit ,
 interlock operating tests ,  mechanical operating tests,  Electrical Equipment operating tests.
ÂÂ
Scope of application
ÂÂ
ÂÂ
It is universally used in power plant ,  electric network , ÂÂ
Metallurgy industry petrochemical industry and infrastructures, Such as airport ,  subway,  building.
VMD2 circuit breaker can be applied to control and protect cable ,
 trolly wire , Transformer,  generator and capacitor bank in distribution system
ÂÂ
Safety
VMD2  circuit breaker possesses  perfect mechanical and electric interlock equipment ,  meanwhile ,
Its high reliable operating performance and mechanical life , ÂÂ
Coodinated with matched switchgear cabinet , To ensure normal power distribution ,  operator and equipment’s safety.