4.1 circuit breakers main fixed parameters (table 1)
- - - -
Serial number | Parameter name | Unit | Specification parameter |
1 | Rated voltage | KV | 40.5 |
2 | 1min labor frequency durable voltage (has effect value) | KV | 95 |
3 | Lightning surge withstanding voltage (peak value) | KV | 185 |
4 | Nominal frequency | Hz | 50 |
5 | Nominal current | A | 1250 ,  1600 ,  2000 |
6 | Fixed short-time withstanding electric current | KA | 25 ,  31.5 |
7 | Fixed peak value withstanding electric current | KA | 63 ,  80 |
8 | The rating short-circuits the duration | S | 4 |
9 | The rating short-circuits the drop-out current | KA | 25 ,  31.5 |
10 | The rating short-circuits the pass to gather the electric current | KA | 63 ,  80 |
11 | Fixed operation sequence |  | O—0.3s—CO—180s—CO |
12 | Opens breaks the time | Ms | ≤80 |
13 | The rating short-circuits the drop-out current to open breaks the number of times | Time | 20 |
14 | Single condenser bank drop-out current | A | 630 |
15 | Back to back condenser bank drop-out current | A | 400 |
16 | Fixed operation voltage | V | AC110/220 ,  DC1100/220 |
17 | Mechanical life | Time | 10000 |
- - - -
4.2, Circuit breaker main physical characteristics parameter (table 2)
- - - -
Serial number | Parameter name | Unit | Specification parameter |
1 | The contact opens the distance | Mm | 20±2 |
2 | Front the contact overtravel | Mm | 7.5±1.5 |
3 | After the average Gathers floodg speed (contact just gathered 12mm) | M/s | 0.8±0.2 |
4 | Evenly to divide equally the floodgate speed (contact just to divide 12mm) | M/s | 1.8±0.2 |
5 | Gathers floodg time | Ms | ≤ 100 |
6 | Minute floodgate time | Ms | ≤ 60 |
7 | The contact Gathers floodg bounces the time | Ms | ≤ 3 |
8 | Three coincides,  divides the floodgate no same time | Ms | ≤ 2 |
9 | Buffer cushion travelling schedule | Mm | 13±1 |
10 | Each return route resistance (including does not touch arm) | μΩ | ≤ 40 |
11 | Contact permission attrition thickness | Mm | 3 |
- - - -
Outline Dimension Drawing
Dear friends, Pls contact us for the outline dimension drawing,  we will give you quick reply.
ZN85-40.5 indoors a.c. high voltage vacuum circuit-breaker (hereafter refers to as circuit breaker) is three phase ac 50HZ,  the rated voltage 40.5kV indoors switching gear.Â
The circuit breaker conforms to GB1984-1989 " high voltage Circuit breaker",  JB3855-1996 "3.6 - 40.5kV Indoors.
 high voltage Vacuum circuit-breaker" and the IEC related standard. The circuit breaker may supply the industry and mining enterprise, Â
The power plant and the transformer substation using of as the analysis and synthesis load current, Â
The excess current,  the fault current,  and is suitable for the frequent operation place.
2  Using Environmental ConditionÂ
2.1 altitudes above sea level: <= 1000mÂ
2.2 ambient temperatures: Highest does not surpass 40 ℃ ,  the daily average value does not surpass 35 ℃ ;Â
Most is lower than -15 ℃ .Â
2.3 environment humidities: The date relative humidity mean value is not bigger than 95%;Â
The date steam pressure mean value does not surpass 2.2kpa;Â
The month relative humidity mean value is not bigger than 90%;Â
The month steam pressure mean value does not surpass 1.8kpa.Â
2.4 earthquake intensities: Is lower than 8 levels ofÂ
2.5 circuit breakers to have to install is not having the fire,  the non- explosion hazard, Â
Non-corrosiveness gas and the not fierce vibration place.Â
2.6 the electronmagetic interference peak-to-peak value which induces in two systems does not surpass 1.6kv.Â
2.7 power sources conditions: Direct current 110V,  220V; Exchanges 110V,  the 220VÂ
2.8 customers like has other special requests,  may when the ordering proposed,
 the our company may give most greatly satisfies.
Scope Of Application
Â
Â
It is universally used in power plant ,  electric network ,
 metallurgy industry petrochemical industry and infrastructures, Such as airport ,  subway,  building.