24kv VMD3 Three - Phase Longitudinal Conductance Circuit Vacuum Circuit Breaker
Technical Parameter
- - - -
NO | Item | Unit | Technical Date |
1 | Rated voltage | KV | 24 |
2 | Rated insulating level | Rated short time power  frequency withstand voltage(1min)          | 65 |
Rated lighting inpulse Withstand voltage (peak value)              | 125 |
3 | Rated Frequency | Hz | 50 |
4 | Rated current | A | 630 |
5 | Rated short circuit breaking current        | KA | 20 |
6 | Rated short time withstand current           | 20 |
7 | Rated peak withstand current  | 50 |
8 | Rated short-circuit closing current (peak value) | 50 |
9 | 4S rated short-time withstand current  4s | 20 |
10 | Rated Dynamic Current | 50 |
11 | Rated making surge current of capacitor bank | 12.5(The frequency is Less than 1000Hz) |
12 | Rated breaking current of single/symmetrical capacitor bank | A | 630/400                               |
13 | Duration of rated short-circuit current | S | 4 |
14 | Power frequency withstand voltage of secondary circuit | V | 2000 |
15 | Rated operationl voltage | Making coil | AC110/220   DC110/220 |
Breaking coil | AC110/220   DC110/220 |
Energy-storage motor | AC110/220   DC110/220 |
16 | Making time  (under Rated voltage) | Ms | ≤60 |
17 | Breaking time(under Rated voltage) | ≤45 |
18 | Permitted abrasion thickness of moving and fixed contacts | Mm | 3 |
19 | Energy storage times | S | ≤15 |
20 | Contactor clearance | Mm | 13± 1 |
21 | Contacting travel | 4±1 |
22 | Bounce time of Contactor during making | Ms | ≤2 |
23 | Different time of breaking / making of 3 phases | ≤2 |
24 | Average breaking speed | 1.1-1.7 |
25 | Average making speed | 0.6-1.1 |
26 | Rebound amplitude of contact breaking | Mm | ≤3 |
27 | Conductance circuit resistance | µΩ | ≤45 (630A) |
28 | Rated operating sequence |   | O- θ -CO-180s-CO |
29 | Mechanical life | Times | 10000 |
- - - -
General Provision
VMD3 lateral fixed type vacuum circuit breaker is our company’s independent developed new product for 12KV/24KV , ÂÂ
Its operating mechanism is new style spring operating mechanism, Developed by our company, ÂÂ
With simple structure and reliable operation.
Product Features
▶ Satisfy the GB, IEC and other international standard
▶ Three-phase longitudinal conductance circuit,
Can be suitable for compound insulation method and solid insulation method
(embedded pole).
▶ Compact structure
▶ Thoroughly meet users’requirements, Suitable for kinds of box-type substation, RMU and switchgear.
▶ Perfect mechanical and electrical interlock device, Further ensure the safe operation.
Testing
VMD3 series circuit breaker have passed has passed followingÂÂ
Test ,  to ensure the product’s safe operation.
ÂÂ
Type tests : power-frequency withstand voltage tests ,  lighting impact withstand voltage tests,  ,  temperature rising tests, ÂÂ
Short-time withstand current tests ,  peak withstand current tests , Short circuit breaking ability tests , ÂÂ
Mechanical lift tests, Ect
ÂÂ
Routine test before out of factory: mechanical performance test  ,  power-frequency withstand voltage tests of the main circuit ,  insulating property  tests on control and auxiliary circuits ,
Measurement of ther resistance of the main circuit ,  interlock operating tests , ÂÂ
Mechanical operating tests,  Electrical Equipment operating tests.
ÂÂ
Scope of application
ÂÂ
It is universally used in power plant ,  electric network ,  metallurgy industry petrochemical industry and infrastructures,
Such as airport ,  subway,  building.
VMD3 circuit breaker can be applied to control and protect cable ,  trolly wire , Transformer, ÂÂ
Generator and capacitor bank in distribution system