Insulating oil tester - Product
Place of Origin : Chongqing,China
Delivery Terms : By Sea
Delivery Time : 30days
Product Capacity : 100
Payment Terms : T/T
Product Description
In the electric power industry, insulating oil is wildly applied in electric equipments. The dielectric strength is a comprehensive index for insulating oil. Series IIJ-II oil tester is special for testing insulating oil's dielectric strength.
Basic Information
Brand : NAKIN
Model : IIJ
Physical Specification
Other Specification : Application:
In The Electric Power Industry, Insulating Oil Is Wildly Applied In Electric Equipments. The Dielectric Strength Is A Comprehensive Index For Insulating Oil. Series IIJ-II Oil Tester Is Special For Testing Insulating Oil's Dielectric Strength. IIJ-II Automatic Oil Tester Is Designed According To International Standard Of IEC156. Adopt Industrial Single Chip As Controller, Apply Large Integrate Circuit, New Type I/O Interface, LCD Displayer, Combined With Special Testing And Anti-jamming Technologies Which Greatly Improve The Tester's Performance.
Features:
1. Simple Operation, High Degree Of Automation (just Press A Button)
2. Using The Menu Management, Easy To Understand The Input Parameters
3. Can Store 99 Groups Oil Sample Test Data To Facilitate Future Access To And Print, Test Data Can Be Stored In Power Off State For 10 Years.
4. The System Clock In The Power Off State Can Continue To Run.
5. Through The RS232 Port With A Software Upgrade Or With The PC, On-line Detection.
6. Anti-interference Ability
7. Detection With High Precision
8. Small Size, Light Weight, Easy Operations
Technical Parameters:
1. Power Supply: AC220V+(-)10%,50Hz
2. Output Voltage: 0 To 100KV(60KV,80KV,100KV)
3. Capacity: 1.2KVA(1.6KVA,2.0KVA)
4. Speed Of Pressure Rise: About 2KV/S
5. Voltage Test Precision:+(-)3%
6. Breakdown Sensitivity: <2KV
7. Wave Difference: <3%
8. Time Of Breakdown: <10ms
9. Working Condition
Temperature: 0C To 40C Humidity : The Biggest Comparatively Humidity85%
10. Reserve Circumstance
Temperature : -20C To 60C Humidity : The Biggest Comparatively Humidity75%
Working Altitude: <1500m (if Over 1500m Can Be Designed Specially)
11. Dimension: 480mm*460mm*460mm