High overload capacity Online Low Frequency UPS GP9310C 10 - 40KVA with 3Ph in/1Ph out - Product
Place of Origin : Shenzhen,China
Delivery Time : 7-15days
Product Description
High overload capacity Online Low Frequency UPS GP9310C 10 - 40KVA with 3Ph in/1Ph out
Key Features
1ph in/1ph out or 3ph in/1ph out, support 380/400/415V, 50/60Hz power system.
Pure-online double conversion technology, to provide the best quality of power supply.
Suitable for all kinds of loads, and a high overload capacity.
Super Wide range of input voltage anti-interferance, adapt to harsh environment in power network.
Intelligent battery management, extending the battery life.
Physical Specification
Other Specification : High Overload Capacity Online Low Frequency UPS GP9310C 10 - 40KVA With 3Ph In/1Ph Out
Key Features
1ph In/1ph Out Or 3ph In/1ph Out, Support 380/400/415V, 50/60Hz Power System.
Pure-online Double Conversion Technology, To Provide The Best Quality Of Power Supply.
Suitable For All Kinds Of Loads, And A High Overload Capacity.
Super Wide Range Of Input Voltage Anti-interferance, Adapt To Harsh Environment In Power Network.
Intelligent Battery Management, Extending The Battery Life.
Large LCD Display In Chinese And English Human-machine Interface.
Technical Specifications Of Online UPS GP9110C GP9310C Series
- - - -
Model | GP9110C6-15KVA | GP9310C10-40KVA |
6KVA | 8KVA | 10KVA | 15KVA | 10KVA | 15KVA | 20KVA | 30KVA | 40KA |
Capacity | 6KVA/ 4.8KW | 8KVA /6.4KW | 10KVA /8KW | 15KVA /12KW | 10KVA /8KW | 15KVA /12KW | 20KVA /16KW | 30KVA /24KW | 40KA /32KW |
Rated Voltage | 220V Single Phase | 380V Three Phase 4 Wires+G |
Rated Frequency | 50/60HZ |
AC Input |
Voltage Range | 220V25% Single Phase | 380V25% Three Phase 4 Wires + G |
Frequency Range | 50/60HZ5% |
Soft Strat | 0-100% 5sec |
Power Factor | 0.92(with Input Filter) |
Bypass Input |
Voltage Range | 220V25% Single Phase | 380V25% Three Phase 4 Wires + G |
Frequency Range | 50/60HZ10% |
Inverter Bypass | (overload)0ms |
| |
Output |
Voltage Accuracy | 220V1%(steady-state Load), 220V3%(load Fluctuations) |
Frequency Accuracy | 50/60Hz0.05Hz(battery Power) |
Power Factor | 0.8(lagging) |
Distortion | <3%(linear Load), <5%(non Linear Load) |
Steady-state Response Time | <10ms |
Overload Capacity | 110%load Can Ru